FERRUPS Online 500VA/350W 120VAC Internal Battery Standard Charger Input/Output Hardwired
- Provides 120V 350watt(s), 500VA power / Surge Suppression is Standard
- Connector(s): Hardwired / 4 Outlets
- 9 minute(s) Battery Runtime at Full Load / Attributes include Double conversion online
The Powerware FERRUPS Tower UPS power supply delivers the best power quality and unmatched reliability in configurable power management. Offering more than just surge protection and backup power, the FERRUPS Tower UPS system features our patented Ferro resonant UPS technology to deliver "bulletproof" power protection.
The FERRUPS Tower UPS offers the ideal level of power protection for banking and security systems, manufacturing process control, servers, and telecommunications equipment.
FERRUPS Online 500VA/350W 120VAC Internal Battery Standard Charger Input/Output Hardwired
|
Connectivity
|
|
|
Communication Interface
|
Contact closure
|
|
# Ports
|
4
|
|
Communication Interface
|
Serial (RS-232)
|
|
Connector
|
Hardwired
|
|
General
|
|
|
Form Factor
|
Tower
|
|
Attributes
|
Double conversion online
|
|
Power
|
|
|
Surge Suppression
|
Standard
|
|
Power Provided
|
120 V
|
|
Power Provided
|
500 VA
|
|
Power Provided
|
350 watt(s)
|
|
Battery Run Time (max)
|
9 minute(s)
|
|
Actual Weight
|
62.00 lb(s)
|
|
Contents
|
UPS, documentation
|
|
Physical Dimensions
|
12"h x 10"w x 21.25"d
|
|
Ports/Connectors
|
Hardwired input and output (1) DB-25 with RS-232 serial communications port, contact closures
|
|
Power Notes
|
Nominal Input Voltage: 120VAC Input Voltage Range: +15%, -20% Input Power Factor: .98 Nominal Output Voltage: 120VAC Output Voltage Regulation: ±3% for input voltages +15% to -20% Output Voltage Waveform: Sine Wave Output Voltage THD: 6% or less at rated kW load Overload Capacity: 150% surge and 125% for 10 minutes on-line. 150% surge and 110% for 10 minutes on inverter. Transfer Time: 0ms Lightning, Surge, and Noise Protection: 2000:1 spike attenuation using ANSI/IEEE C62.41 and C62.45 Category A and Category B tests; Common Mode ->120 dB.Normal Mode ->60dB Efficiency: 85% Typical On-battery runtime, half load: 25 minutes (175W) Typical On-battery runtime, full load: 9 minutes (350W)
|
|
Returns Policy
|
This product is subject to our return policy. Please see our complete return policy for details.
|
|
Warranty - Labor
|
2 Years
|
|
Warranty - Parts
|
2 Years
|
|
Warranty Details
|
$250, 000 load protection guarantee
|
FERRUPS Online 500VA/350W 120VAC Internal Battery Standard Charger Input/Output Hardwired
1
Year PC Connection Consumer Electronic Coverage ($1,001 - $1,500), EXT
2
Year PC Connection Consumer Electronic Coverage ($1,001 - $1,500), EXT
FERRUPS Online 500VA/350W 120VAC Internal Battery Standard Charger Input/Output Hardwired
http://www.macconnection.com/IPA/Shop/Product/Detail.htm?sku=6388982#BVSecondaryCustomerRatings